  3. School: a hissing classroom and a saturated field

Leaking supply capped and retested by ADISchool · West Yorkshire

Buried pipe leak under a classroom floor, traced with tracer gas and acoustics

The meter was passing a litre every five seconds and one classroom was hissing. Isolation, tracer gas and acoustic listening found a leak on the buried pipe to a single desk tap, which ADI capped off and pressure tested.

Blue acoustic leak detection amplifier with a ground listening probe and ear defenders on a wooden worktop
ADI photograph from this job: the acoustic listening kit used to follow the leak on the buried pipe.

What was happening

The school had received a notice that it had a leak. Staff had also noticed a hissing noise in one of the classrooms. Outside, the external meter was passing one litre every five seconds, and the part of the field nearest that classroom was saturated.

What the engineer did

The engineer timed the meter, walked the site and found the wet ground. Closing the stopcock for that part of the building stopped the hissing and slowed the meter right down, so the leak was on that branch. Tracer gas was put into the pipework on that side of the building and detected inside the hissing classroom, and acoustic equipment then picked up water moving on the buried pipe beneath the floor.

What was found

The leak was on buried pipework under the concrete floor, on the supply to the teacher's desk tap in that classroom.

What happened next

The engineer explained the two options: dig out the pipe for a full repair, which meant removing cupboards, or cap off the supply to the desk tap. The school chose to cap it. ADI fitted a 15 mm compression stop end, then pressure tested that side of the building at 3 bar for 30 minutes with no drop, confirming no other leaks on that supply.

If you look after an office building

Sometimes the cheapest fix is not a repair at all. When a leaking buried pipe only feeds one outlet that nobody relies on, capping it off saves digging up a working room, and a pressure test afterwards proves the rest of the supply is sound.